Highlights: Automatic gas cylinder changeover for vapor phase
(Automatic Vapor Changeover)
Operation: Automatically switches LPG vapor supply
from the primary cylinder bank to the reserve bank when primary pressure
drops below the threshold, ensuring stable and continuous fuel flow to the system line.
Safety: Hermetically sealed diaphragm chamber provides excellent leak prevention.
Dual flanged connections (left-right)
enhance structural integrity and minimize leakage risks at connection points.
Suitable for: LPG supply systems in commercial buildings, restaurants, or small-to-medium industrial plants utilizing direct vapor phase piping from cylinder banks.
Model: HAX-35B
Capacity: 35 kg/h
Inlet Pressure: 0.2-1.6 MPa
Outlet Pressure: 0.1-0.16 MPa
Outlet Pressure Supply Setting: 0.14 MPa
Outlet Pressure Reserve Setting: 0.11 MPa
Inlet Connection: Flange KS/JIS 15A-20K
Outlet Connection: PT 1/2
We select recommended products that ensure comprehensive system compatibility to prevent errors
and enhance installation safety for you.